Rule ID: 22-4
Schema Version: 0.0.23
Rule Description: For Baseline chilled water loop that is not purchased chilled water and does not serve any computer room HVAC systems, chilled-water supply temperature shall be reset using the following schedule: 44F at outdoor dry-bulb temperature of 80F and above, 54F at 60F and below, and ramped linearly between 44F and 54F at temperature between 80F and 60F.
Rule Assertion: B-RMR = expected value
Appendix G Section: Section 22 CHW&CW Loop
Appendix G Section Reference: Section G3.1.3.9 Chilled-water supply temperature reset (System 7, 8, 11, 12 and 13)
Applicability: All required data elements exist for B_RMR
Applicability Checks:
- B-RMR is modeled with at least one air-side system that is Type-7, 8, 12, 13, 7b, 8b, 12b.
- B-RMR is not modeled with any air-side system that is Type-11.1, 11.2, 11.1a, 11.2a, 11b or 11c.
Manual Check: None
Evaluation Context: Building
Data Lookup: None
Function Call:
- get_baseline_system_types()
Applicability Checks:
-
Get B-RMR system types:
baseline_hvac_system_dict = get_baseline_system_types(B-RMR)
-
Check if B-RMR is modeled with at least one air-side system that is Type-7, 8, 12, 13, 7b, 8b, 12b, 13b, i.e. with air-side system served by chiller(s), continue to rule logic:
if any(sys_type in baseline_hvac_system_dict.keys() for sys_type in ["SYS-7", "SYS-8", "SYS-12", "SYS-13", "SYS-7B", "SYS-8B", "SYS-12B"]):
-
Check if B-RMR is modeled with any air-side system that is Type-11.1, 11.2, 11.1a, 11.2a, 11b or 11c, rule is not applicable to B-RMR:
if any(sys_type in baseline_hvac_system_dict.keys() for sys_type in ["SYS-11.1", "SYS-11.2", "SYS-11.1A", "SYS-11.2A", "SYS-11B", "SYS-11C"]): RULE_NOT_APPLICABLE
-
Else, continue to rule logic:
else: CHECK_RULE_LOGIC
-
-
Else, rule is not applicable to B-RMR:
else: RULE_NOT_APPLICABLE
-
-
For each chiller in B_RMR, save chiller to loop-chiller-ids-list:
for chiller_b in B_RMR.ASHRAE229.chillers: chiller_loop_ids_list.append(chiller_b)
-
For each fluid loop in B_RMR:
for fluid_loop_b in B_RMR.ASHRAE229.fluid_loops:
-
Check if fluid loop is connected to chiller(s):
if fluid_loop_b.id in loop_chiller_dict.keys()
Rule Assertion - Component:
-
Case 1: For Baseline chilled water loop that is not purchased cooling and does not serve any Baseline System Type-11, if chilled-water supply temperature is reset to 44F at outdoor dry-bulb temperature of 80F and above, 54F at 60F and below, and ramped linearly between 44F and 54F at temperature between 80F and 60F:
if ( fluid_loop_b.cooling_or_condensing_design_and_control.outdoor_high_for_loop_supply_reset_temperature == 80 ) AND ( fluid_loop_b.cooling_or_condensing_design_and_control.outdoor_low_for_loop_supply_reset_temperature == 60 ) AND ( fluid_loop_b.cooling_or_condensing_design_and_control.loop_supply_temperature_at_outdoor_high == 44 ) AND ( fluid_loop_b.cooling_or_condensing_design_and_control.loop_supply_temperature_at_outdoor_low == 54 ): PASS
-
Case 2: Else:
else: FAIL
-
-