CHW&CW - Rule 22-4

Rule ID: 22-4
Schema Version: 0.0.23 Rule Description: For Baseline chilled water loop that is not purchased chilled water and does not serve any computer room HVAC systems, chilled-water supply temperature shall be reset using the following schedule: 44F at outdoor dry-bulb temperature of 80F and above, 54F at 60F and below, and ramped linearly between 44F and 54F at temperature between 80F and 60F.
Rule Assertion: B-RMR = expected value
Appendix G Section: Section 22 CHW&CW Loop
Appendix G Section Reference: Section G3.1.3.9 Chilled-water supply temperature reset (System 7, 8, 11, 12 and 13)

Applicability: All required data elements exist for B_RMR
Applicability Checks:

  1. B-RMR is modeled with at least one air-side system that is Type-7, 8, 12, 13, 7b, 8b, 12b.
  2. B-RMR is not modeled with any air-side system that is Type-11.1, 11.2, 11.1a, 11.2a, 11b or 11c.

Manual Check: None
Evaluation Context: Building
Data Lookup: None
Function Call:

  1. get_baseline_system_types()

Applicability Checks:

  • Get B-RMR system types: baseline_hvac_system_dict = get_baseline_system_types(B-RMR)

    • Check if B-RMR is modeled with at least one air-side system that is Type-7, 8, 12, 13, 7b, 8b, 12b, 13b, i.e. with air-side system served by chiller(s), continue to rule logic: if any(sys_type in baseline_hvac_system_dict.keys() for sys_type in ["SYS-7", "SYS-8", "SYS-12", "SYS-13", "SYS-7B", "SYS-8B", "SYS-12B"]):

      • Check if B-RMR is modeled with any air-side system that is Type-11.1, 11.2, 11.1a, 11.2a, 11b or 11c, rule is not applicable to B-RMR: if any(sys_type in baseline_hvac_system_dict.keys() for sys_type in ["SYS-11.1", "SYS-11.2", "SYS-11.1A", "SYS-11.2A", "SYS-11B", "SYS-11C"]): RULE_NOT_APPLICABLE

      • Else, continue to rule logic: else: CHECK_RULE_LOGIC

    • Else, rule is not applicable to B-RMR: else: RULE_NOT_APPLICABLE

Rule Logic:

  • For each chiller in B_RMR, save chiller to loop-chiller-ids-list: for chiller_b in B_RMR.ASHRAE229.chillers: chiller_loop_ids_list.append(chiller_b)

  • For each fluid loop in B_RMR: for fluid_loop_b in B_RMR.ASHRAE229.fluid_loops:

    • Check if fluid loop is connected to chiller(s): if fluid_loop_b.id in loop_chiller_dict.keys()

      Rule Assertion - Component:

      • Case 1: For Baseline chilled water loop that is not purchased cooling and does not serve any Baseline System Type-11, if chilled-water supply temperature is reset to 44F at outdoor dry-bulb temperature of 80F and above, 54F at 60F and below, and ramped linearly between 44F and 54F at temperature between 80F and 60F: if ( fluid_loop_b.cooling_or_condensing_design_and_control.outdoor_high_for_loop_supply_reset_temperature == 80 ) AND ( fluid_loop_b.cooling_or_condensing_design_and_control.outdoor_low_for_loop_supply_reset_temperature == 60 ) AND ( fluid_loop_b.cooling_or_condensing_design_and_control.loop_supply_temperature_at_outdoor_high == 44 ) AND ( fluid_loop_b.cooling_or_condensing_design_and_control.loop_supply_temperature_at_outdoor_low == 54 ): PASS

      • Case 2: Else: else: FAIL