Boiler - Rule 21-11

Rule ID: 21-11
Rule Description: The baseline building design uses boilers or purchased hot water, the hot water pumping system shall be modeled as primary-only.
Rule Assertion: B-RMR
Appendix G Section: Section 21 Boiler
Appendix G Section Reference: Section G3.1.3.5 Building System-Specific Modeling Requirements for the Baseline model

Applicability: All required data elements exist for B_RMR
Applicability Checks:

  1. B-RMR is modeled with at least one air-side system that is Type-1, 5, 7, 11.2, 12, 1a, 7a, 11.2a, 12a, 1b, 3b, 5b, 6b, 7b, 8b, 9b, 11b, 12b, 1c, 3c, 7c, 8c, 11c.

Evaluation Context: Building
Data Lookup: None
Function Call:

  1. get_baseline_system_types()

Applicability Checks:

  • Get B-RMR system types: baseline_hvac_system_dict = get_baseline_system_types(B-RMR)

    • Check if B-RMR is modeled with at least one air-side system that is Type-1, 5, 7, 11.2, 12, 1a, 7a, 11.2a, 12a, 1b, 3b, 5b, 6b, 7b, 8b, 9b, 11b, 12b, 13b, 1c, 3c, 7c, 8c, 11c, 13c, continue to rule logic: if any(sys_type in baseline_hvac_system_dict.keys() for sys_type in ["SYS-1", "SYS-5", "SYS-7", "SYS-11.2", "SYS-12", "SYS-1A", "SYS-7A", "SYS-11.2A", "SYS-12A", "SYS-1B", "SYS-3B", "SYS-5B", "SYS-6B", "SYS-7B", "SYS-8B", "SYS-9B", "SYS-11B", "SYS-12B", "SYS-13B", "SYS-1C", "SYS-3C", "SYS-7C", "SYS-11C", "SYS-13C"]): CHECK_RULE_LOGIC

    • Else, rule is not applicable to B-RMR: else: RULE_NOT_APPLICABLE

Rule Logic:

  • For each fluid loop in B_RMR: for fluid_loop_b in B_RMR.RulesetModelInstance.fluid_loops:

    • Check if fluid loop type is heating: if fluid_loop_b.type == "HEATING"

      Rule Assertion - Component:

      • Case 1: For each heating hot water loop, if loop is modeled as primary only: if fluid_loop_b.child_loop == NULL: PASS

      • Case 2: Else: else: FAIL

Note

  1. Updated the Rule ID from 21-11A to 21-11 on 7/26/2022