Rule ID: Rule 15-6
Rule Description: Transformer efficiency reported in User RMR equals Table 8.4.4
Rule Assertion: User RMR = expected value
Appendix G Section: Transformers
Appendix G Section Reference: Table G3.1 15. Distribution Transformers
Data Lookup: Table 8.4.4
Evaluation Context: Each Data Element
Applicability Checks:
- Transformer is DRY_TYPE
- U_RMR transformer capacity is within range of Table 8.4.4
Manual Checks: None
- For each transformer
_user_transformer
inU_RMR.transformers
:- Get maximum regulated capacity:
if user_transformer.phase == SINGLE_PHASE: _max_capacity_limit = 333.0 else if user_transformer.phase == THREE_PHASE: _max_capacity_limit = 1000.0
- Applicability Check 1:
_user_transformer.type == DRY_TYPE
- Applicability Check 2:
_user_transformer.capacity >= 15.0 and _user_transformer.capacity <= _max_capacity_limit:
- Get required User transformer efficiency:
required_user_transformer_efficiency = data_lookup(table_8_4_4, _user_transformer.capacity, _user_transformer.phase)
- Rule Assertion:
user_transformer.efficiency == required_user_transformer_efficiency
- Get maximum regulated capacity: