Nefit Moduline 3000 loses connection to external temperature sensor on HRC45 -- ERROR A11/1037 #2059
Comments
The outdoor sensor is direct connected to the boiler and published in 0x19 telegram. Haven't you got A01(800) error in the log? |
Happened again this morning and I measured the sensor but got a stable 20,58 kOhm value. The thermostat recovered and things resumed to normal. I have logging enabled and will keep an eye out when this happens again. Will also check the sensor housing for spiders |
Error just happened again, I can confirm the error code on the thermostat and that the sensor appears to operate normally (I can see it on the boiler itself through the info button) Problem started around 17h05. Below are the logs, there are some gaps as the logs were flooded: Due to the size I could not post the logs directly. If I disconnect the thermostat and reconnect then the error disappears and returns a few minutes later. |
Happened again twice, now running dev42 build. I could not find any log entries
But after that initial message it remains quiet and the thermostat loses the outdoor temperature reading again after approx. 4 minutes. I can see a lot of UBAMonitorSlow messages in the logs but they are between boiler and controller. I'm not sure what the controller is since I only see a boiler and a thermostat in my devices overview.
After a while the situation resolves itself and the problem goes away. I don't know why or when that happens, the logs are too short |
Seems like I have the same / a similar problem with my setup, after upgrading to 3.7.x dev end of September on a BBQKees Gateway E32 V1. During Summer with the Boiler in Summer Mode (heating switched off and only hot water active) I did not notice any errors, and no errors were stored in the RC310 error log. I have the following devices on my BUS From monitoring in home assistant I can see that every ~48 hours I get the following errors: The boiler itself does not loose connection to the temp sensor, but the RC310 does and commands the boiler to heat up as if it freezes outside. After some minutes the system recovers by itself and my heating returns to normal operation. I just downgraded to 3.6.5 again to verify the errors do not occure with this verison. |
My System configuration as of with Firmware v3.6.5: If the errors do not occure with the stable version I'll update again to 3.7.x to collect more information if it helps. |
I keep having this error popping up, have not downgraded yet. I switched the protocol to EMS+ (as I noticed the newer Moduline 3000 supperted that) but that doesn't make a difference. I posted the logs as @proddy requested but he has not provided any additional guidance so far. |
@Moving4407 |
I tried blocking writes from EMS-ESP but this does not help. Other suggestions (or requests for data) welcome, don't really know what/where to look |
I can only confirm that the errors do not occure again after downgrading to 3.6.5. |
Hi, got the same error with Junkers ZSB14 and CW400. Before 3.7.0 everything was fine |
Hi, it seems that 3.7.1 fixed this issue? After Updating i dont get the error anymore same for you? |
Yes, in my System the Errors did not occure again since the update to 3.7.1. |
DESCRIPTION
After 2-3 days of running the outside temperature disappears from the Moduline 3000 thermostat display and the thermostat starts heating (weather-controlled program). This behavior was not present in v3.6.5. Unplugging the EMS gateway resolves the issue (the temperature appears again). This behavior does not occur on a similar setup (HRC 30 with older Moduline 3000)
REQUESTED INFORMATION
system |
version | "3.7.0-dev.39"
uptime | "003+00:36:42.569"
uptimeSec | 261402
platform | "ESP32S3"
cpuType | "ESP32-S3"
arduino | "ESP32 Arduino v2.0.17"
sdk | "v4.4.7-dirty"
freeMem | 194
maxAlloc | 179
freeCaps | 8336
usedApp | 2237
freeApp | 5891
partition | "app0"
resetReason | "Power on reset / Power on reset"
psram | true
psramSize | 8189
freePsram | 8143
model | ""
network |
network | "WiFi"
hostname | "nefit-HRC45"
RSSI | -52
TxPowerSetting | 0
staticIP | false
lowBandwidth | false
disableSleep | true
enableMDNS | true
enableCORS | false
APProvisionMode | "disconnected"
APSecurity | "wpa2"
APSSID | "ems-esp"
ntp |
NTPStatus | "connected"
enabled | true
server | "ntp.time.nl"
tzLabel | "Europe/Amsterdam"
mqtt |
MQTTStatus | "connected"
MQTTPublishes | 82975
MQTTQueued | 0
MQTTPublishFails | 0
MQTTConnects | 1
enabled | true
clientID | "ems-esp-nefit-HRC45"
keepAlive | 60
cleanSession | false
entityFormat | 2
base | "ems-esp-nefit-HRC45"
discoveryPrefix | "homeassistant"
discoveryType | 0
nestedFormat | 1
haEnabled | true
mqttQos | 0
mqttRetain | false
publishTimeHeartbeat | 60
publishTimeBoiler | 10
publishTimeThermostat | 10
publishTimeSolar | 10
publishTimeMixer | 10
publishTimeWater | 10
publishTimeOther | 10
publishTimeSensor | 10
publishSingle | false
publish2command | false
sendResponse | false
syslog |
enabled | false
sensor |
temperatureSensors | 7
temperatureSensorReads | 365948
temperatureSensorFails | 0
analogSensors | 0
analogSensorReads | 0
analogSensorFails | 0
api |
APICalls | 2
APIFails | 0
bus |
busStatus | "connected"
busProtocol | "Buderus"
busTelegramsReceived | 261138
busReads | 78550
busWrites | 0
busIncompleteTelegrams | 12
busReadsFailed | 0
busWritesFailed | 0
busRxLineQuality | 100
busTxLineQuality | 100
settings |
boardProfile | "S32S3"
locale | "en"
txMode | 1
emsBusID | 11
showerTimer | false
showerMinDuration | 180
showerAlert | false
hideLed | false
noTokenApi | false
readonlyMode | false
fahrenheit | false
dallasParasite | false
boolFormat | 1
boolDashboard | 1
enumFormat | 1
analogEnabled | true
telnetEnabled | true
maxWebLogBuffer | 50
webLogBuffer | 33
modbusEnabled | false
forceHeatingOff | false
devices |
0 |
type | "boiler"
name | "Topline/GB162"
deviceID | "0x08"
productID | 115
brand | ""
version | "05.09"
entities | 76
handlersReceived | "0x10 0x11 0x15 0x1C 0x18 0x19 0x34 0x04"
handlersFetched | "0x14 0x16 0x33"
handlersPending | "0xBF 0xC2 0x1A 0x35 0x26 0x2A 0xD1 0xE3 0xE4 0xE5 0xE6 0xE9 0xEA 0x28 0x2E 0x3B"
1 |
type | "thermostat"
name | "RC300/RC310/Moduline 3000/1010H/CW400/Sense II/HPC410"
deviceID | "0x10"
productID | 158
brand | ""
version | "74.03"
entities | 58
handlersReceived | "0x06 0xA2 0x02BA 0x02BB 0x02BC 0x02BE 0x02BF 0x02C0 0x031D 0x0267"
handlersFetched | "0x02A5 0x02B9 0x02AF 0x029B 0x0291 0x0292 0x0293 0x0294 0x02F5 0x02F6 0x031B 0x023A 0x0240 0x0269"
handlersPending | "0xA3 0x12 0x13 0x0471 0x02A6 0x02B0 0x029C 0x0472 0x02A7 0x02B1 0x029D 0x0473 0x02A8 0x02B2 0x029E 0x0474 0x02A9 0x02BD 0x02B3 0x029F 0x0475 0x02AA 0x02B4 0x02A0 0x0476 0x02AB 0x02B5 0x02A1 0x0477 0x02AC 0x02B6 0x02A2 0x0478 0x02CC 0x0467 0x02CE 0x0468 0x02D0 0x0469 0x02D2 0x046A 0x031E 0xBB 0x023E"
handlersIgnored | "0xBF"
2 |
type | "controller"
name | "BC10"
deviceID | "0x09"
productID | 114
brand | ""
version | "01.03"
entities | 0
handlersIgnored | "0x04 0x16 0x1C 0x33 0x24 0x10 0x18 0x19"
TO REPRODUCE
Plug in the gateway, wait for 2-3 days and the outside temperate disappears from the thermostat. This happened twice now. When I plug the gateway back in the system continues to operate normally until after a couple of days.