Skip to content

Files

Latest commit

 

History

History
 
 

Folders and files

NameName
Last commit message
Last commit date

parent directory

..
Mar 3, 2022
Mar 3, 2022

SNMP APC PDU

Overview

UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now!

This APC Template contains outlet discovery and should work with any managed or switched APC PDU.

Contains sane triggers, load status, graphs, etc.

Triggers: APC Load State, Load Change, Power Alarm, etc.

Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more.

Graphs: Load and Current

Outlet Status (Dynamic Discovery)

Please enjoy and vote!

Macros used

Name Description Default Type
{$SNMP_COMMUNITY}

-

public Text macro

Template links

There are no template links in this template.

Discovery rules

Name Description Type Key and additional info
Outlets

-

SNMP agent rPDU2Outlet

Update: 3600

Items collected

Name Description Type Key and additional info
rPDU2DeviceStatusPeakPower.1

-

SNMP agent rPDU2DeviceStatusPeakPower.1

Update: 300

rPDU2IdentName.1

-

SNMP agent rPDU2IdentName.1

Update: 86400

rPDU2PhaseStatusPeakCurrent.1

-

SNMP agent rPDU2PhaseStatusPeakCurrent.1

Update: 30

rPDU2IdentFirmwareRev.1

-

SNMP agent rPDU2IdentFirmwareRev.1

Update: 600

rPDU2PhaseStatusVoltage.1

-

SNMP agent rPDU2PhaseStatusVoltage.1

Update: 30

sPDUMasterState.0

-

SNMP agent sPDUMasterState.0

Update: 60

rPDU2DevicePropertiesMaxPhaseCurrentRating.1

-

SNMP agent rPDU2DevicePropertiesMaxPhaseCurrentRating.1

Update: 86400

rPDU2PhaseStatusCurrent.1

-

SNMP agent rPDU2PhaseStatusCurrent.1

Update: 30

rPDU2DeviceStatusPowerSupplyAlarm.1

-

SNMP agent rPDU2DeviceStatusPowerSupplyAlarm.1

Update: 30

rPDU2DeviceStatusPeakPowerTimestamp.1

-

SNMP agent rPDU2DeviceStatusPeakPowerTimestamp.1

Update: 300

rPDU2IdentLocation.1

-

SNMP agent rPDU2IdentLocation.1

Update: 86400

rPDU2GroupTotalEnergy.0

-

SNMP agent rPDU2GroupTotalEnergy.0

Update: 30

sPDUIdentModelNumber.0

-

SNMP agent sPDUIdentModelNumber.0

Update: 86400

rPDU2PhaseStatusPeakCurrentTimestamp.1

-

SNMP agent rPDU2PhaseStatusPeakCurrentTimestamp.1

Update: 300

rPDU2IdentModelNumber.1

-

SNMP agent rPDU2IdentModelNumber.1

Update: 86400

rPDU2DeviceStatusPower.1

-

SNMP agent rPDU2DeviceStatusPower.1

Update: 30

rPDU2IdentSerialNumber.1

-

SNMP agent rPDU2IdentSerialNumber.1

Update: 86400

sPDUMasterPending.0

-

SNMP agent sPDUMasterPending.0

Update: 60

rPDU2DeviceStatusLoadState.1

-

SNMP agent rPDU2DeviceStatusLoadState.1

Update: 30

sPDUIdentFirmwareRev.0

-

SNMP agent sPDUIdentFirmwareRev.0

Update: 600

Outlet $1 Name

-

SNMP agent rPDU2OutletSwitchedConfigName[{#SNMPINDEX}]

Update: 3600

LLD

Outlet $1 Bank

-

SNMP agent rPDU2OutletSwitchedPropertiesBank[{#SNMPINDEX}]

Update: 86400

LLD

Outlet $1 State

-

SNMP agent rPDU2OutletSwitchedStatusState[{#SNMPINDEX}]

Update: 60

LLD

Triggers

Name Description Expression Priority
Outlet {#SNMPVALUE} State Change

-

Expression: (last(/SNMP APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#1)<>last(/SNMP APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#2))=1

Recovery expression:

information
Outlet {#SNMPVALUE} State Change (LLD)

-

Expression: (last(/SNMP APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#1)<>last(/SNMP APC PDU/rPDU2OutletSwitchedStatusState[{#SNMPINDEX}],#2))=1

Recovery expression:

information

SNMP Tripplite

Overview

UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now!

This APC Template contains outlet discovery and should work with any managed or switched APC PDU.

Contains sane triggers, load status, graphs, etc.

Triggers: APC Load State, Load Change, Power Alarm, etc.

Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more.

Graphs: Load and Current

Outlet Status (Dynamic Discovery)

Please enjoy and vote!

Overview

UPDATE: Uploaded V2 to fix one of the power ratings that was the wrong OID. It was collecting watts incorrectly. All fixed now!

This APC Template contains outlet discovery and should work with any managed or switched APC PDU.

Contains sane triggers, load status, graphs, etc.

Triggers: APC Load State, Load Change, Power Alarm, etc.

Items: Basic information (model, name, firmware, etc), Power load/peak/etc, Master States (Enable for older units), All APC value mappings, and much more.

Graphs: Load and Current

Outlet Status (Dynamic Discovery)

Please enjoy and vote!

Macros used

There are no macros links in this template.

Template links

There are no template links in this template.

Discovery rules

There are no discovery rules in this template.

Items collected

Name Description Type Key and additional info
upsBypassPower.1

-

SNMP agent upsBypassPower.1

Update: 30

upsIdentAgentSoftwareVersion

-

SNMP agent upsIdentAgentSoftwareVersion

Update: 600

upsOutputFrequency

-

SNMP agent upsOutputFrequency

Update: 30

upsBypassCurrent.1

-

SNMP agent upsBypassCurrent.1

Update: 30

upsAlarmsPresent

-

SNMP agent upsAlarmsPresent

Update: 30

upsBypassFrequency

-

SNMP agent upsBypassFrequency

Update: 30

upsSecondsOnBattery

-

SNMP agent upsSecondsOnBattery

Update: 30

upsIdentUPSSoftwareVersion

-

SNMP agent upsIdentUPSSoftwareVersion

Update: 600

upsInputVoltage.1

-

SNMP agent upsInputVoltage.1

Update: 30

upsBatteryTemperature

-

SNMP agent upsBatteryTemperature

Update: 60

upsEstimatedChargeRemaining

-

SNMP agent upsEstimatedChargeRemaining

Update: 60

upsInputFrequency.1

-

SNMP agent upsInputFrequency.1

Update: 30

upsBypassVoltage.1

-

SNMP agent upsBypassVoltage.1

Update: 30

upsEstimatedMinutesRemaining

-

SNMP agent upsEstimatedMinutesRemaining

Update: 30

upsInputLineBads

-

SNMP agent upsInputLineBads

Update: 30

upsOutputVoltage.1

-

SNMP agent upsOutputVoltage.1

Update: 30

upsOutputCurrent.1

-

SNMP agent upsOutputCurrent.1

Update: 30

upsOutputPower.1

-

SNMP agent upsOutputPower.1

Update: 30

upsBatteryVoltage

-

SNMP agent upsBatteryVoltage

Update: 60

upsOutputPercentLoad.1

-

SNMP agent upsOutputPercentLoad.1

Update: 30

upsOutputSource

-

SNMP agent upsOutputSource

Update: 30

upsBatteryStatus

-

SNMP agent upsBatteryStatus

Update: 30

upsIdentModel

-

SNMP agent upsIdentModel

Update: 86400

Triggers

There are no triggers in this template.